F753 - PROFIBUS Interface Board

3U CompactPCI

The F753 is a single Eurocard CompactPCI PROFIBUS controller that needs only one slot on the CompactPCI bus.

  • F753 Product ImageF753 3U CompactPCI PROFIBUS Interface Board
  • F753 Product ImageF753 PROFIBUS controller
  • F753 Product ImageF753 PROFIBUS controller
  • F753 Product Image
  • F753 Product Image
  • F753 Product Image

Main Features

  • 4HP 32-bit/33-MHz CompactPCI<br />Isolated RS485 interface<br />PROFIBUS DP master, DP slave and MPI device determined by loadable firmware<br />Based on netX universal network controller<br />Isolation with 1000 VDC voltage<br />Driver support for all common operating systems<br />-20 °C to +70 °C
F753 Product Image

Technical Data

PROFIBUS
  • Supported communication determined by firmware:
    • PROFIBUS DP Master
    • PROFIBUS DP Slave
    • PROFIBUS MPI Device
  • PROFIBUS Interface
    • Type RS 485
    • Isolated
    • 9-pin D-Sub receptacle connector
Communication Controller
Hilscher netX 100 SOC
Integrated Memory
  • 8 MB SDRAM
  • 4 MB serial Flash EPROM
  • 64 KB Dual-Port Memory (DPM)
Diagnostic Interface
Mini B USB plug (5-pin)
LED Display
  • System status LED
  • LED Communication Status (duo LED)
CompactPCI Bus
  • Compliant with PICMG 2.0 R2.1
  • 32-bit/33-MHz bridge
  • DPM or DMA data access
Electrical Specifications
  • Supply voltage/maximum current
    • +3.3 V DC ±5% / 650 mA
  • Connected via CompactPCI Bus
Mechanical Specifications
  • Dimensions (L x W x H): 162.2 x 100 x 20 mm
  • CompactPCI slot (3.3 V)
  • Weight: 134 g
Environmental Conditions
  • Temperature range (operation): -20..+70°C
  • Temperature range (storage): -10..+70°C
  • Relative humidity: max. 95% non-condensing
CE Conformity
  • EN 55011:2009 + A1:2010, CISPR 11:2009, Class A (radio disturbance)
  • EN 61000-4-2:2009 (electrostatic discharge)
  • EN 61000-4-3:2006 + A1:2008 + A2:2010 (radiated, radio-frequency, electromagnetic field immunity)
  • EN 61000-4-4:2004 + A1:2010 (burst electrical fast transients/burst)
  • EN 61000-4-5:2006 (surge)
  • EN 61000-4-6:2009 (to conducted disturbances, induced by radio- frequency fields)
  • EN 61000-4-8:2010 (power frequency magnetic field)
  • EN 61000-6-2:2005 + B1:2011 (for industrial environments)
Certification
The device is certified according to UL 508
  • UL-File-Nr. E221530
Operating Systems
  • Windows
  • Windows CE
  • Linux
  • VxWorks
  • QNX
Software and Drivers
  • Configuration software master and slave:
    • SYCON.net
  • Configuration software slave:
    • netX Configuration Tool
  • For more information regarding drivers and software, please visit:
    • CompactPCI Communication Interface for PROFIBUS Master
    • CompactPCI Communication Interface for PROFIBUS Slave
Support and Downloads
For more information on supported operating system versions and drivers see Software.

Ordering Information

Standard F753 Models
02F753-00

1 PROFIBUS DP Slave interface, -20..+70°C screened

02F753-01

1 PROFIBUS DP Master interface, -20..+70°C screened

Contact Request! Use this form to get the fastest possible reply.
Please make sure to fill out the complete form, so we can provide quick and specific support.
Your request will be sent to our sales team.

Your information will not be shared!

* required fields

Your Request

Your Contact Data

Please type in the letters and/or numbers that you see in the image on the left (case-sensitive).